Advanced protection relay test set GFUVE Test-330 secondary injection relay test set with excellent working performance

FOB Reference Price:Get Latest Price
US $0-5,000 / Set | 1 Set/Sets (Min. Order)
Supply Ability:
5000 Set/Sets per Year
Port:
Beijing/Shenzhen
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Beijing, China (Mainland)
Brand Name:
GFUVE
Model Number:
Test-330
Power:
Electronic
Usage:
Auto Testing Machine
Test-330:
Advanced secondary injection relay test set
Measuring Voltage Range:
0~650V
Measuring Current Range:
0~90A
Dimensions:
360mmx195mm x375mm
Operating Temperature:
0~45℃
output:
260VA/phase
Phase voltage output (effective value):
5x0~130V
Line voltage output (effective value):
0~260V
maximum output power:
70VA/phase
accuracy:
<±0.2%
Packaging & Delivery
Packaging Details
Inside a layer of aluminum alloy box, outside is packed in wooden cases
Delivery Time
11days upoin receipt of firm order

Specifications

1. Embedded host machine equipped with Complex
2.Programmable Logic Device (CPLD)
3. Eight-path synchronous D/A output

  Power plant and substation testing device dc high voltage test set Test-330 secondary injection relay test set ,substation electrical safety equipment,with CE,ISO9001:2008,IEC approved,english version display and operation,two years quality warranty.

Features

1. Embedded host machine equipped with Complex Programmable Logic Device (CPLD)

2. Eight-path synchronous D/A output in a single machine.

3. High-accuracy linear power amplifier and synchronous output of five-phase voltage and three-phase current.

4. Host machine-integrated single cabinet structure with big screen LCD and complete interface has obtained appearance patent..

5. Intelligent self-protection.

6. Plentiful Binary and powerful software function.

Technical Parameters

Main rated parameters

AC current output

Test-330

Phase current output (effective value)       3×0~30A

Maximum output power        260VA/phase

Maximum parallel current output (effective value) 0~90A

Long-term allowable working value of phase current (effective value) >10A

Allowable working time of maximum current       >11s

Accuracy <±0.2%

AC voltage output

Test-330

Phase voltage output (effective value)   5×0~130V

Line voltage output (effective value)       0~260V

Maximum output power  70VA/phase

Accuracy             <±0.2%

DC voltage output

Test-330

Output range      0~300V or 5×0~±130V

Maximum output power           130VA

Accuracy                    <±0.2%

DC current output

Test-330

Output range       -10~10A or 3×0~±10A

Maximum output power            200VA

Accuracy                    <±0.2%

Binary input

Idle contact       1~20mA, 24V (DC)

Electric potential contact         0~250V (DC)

Binary output

Idle contact             250V/0.5A (DC)

Other rated parameters

Rated output

Frequency error     <±0.01Hz

Phase error             <±0. 2°

Waveform distortion    <±0.3% (fundamental wave)

Time error                 <40µs

Output frequency    0~1050Hz

Superposed harmonic wave0~21times

Power voltage

Allowable range      AC220V±10%, 50Hz±10%

Ambient temperature

Use range                 0~45°C

Storage range            -25~70°C

Time measurement

Test range         0.1ms~999999.999s

Exterior appearance of cabinet

Imported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected.

Dimension of cabinet: length×width×height360mm ×195mm ×375mm

Weight of cabinet

Weight of host machine     16.6kg

Load-bearing output

Selectable between light load or heavy load output

(When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode)

 

 

Company Introduction

Certifications

Trading Process

Packaging & Shipping

Services