Single phase test bench GFUVE GF102 watt-hour meter calibrator

FOB Reference Price:Get Latest Price
US $0-4,000 / Set | 1 Set/Sets (Min. Order)
Supply Ability:
100 Set/Sets per Month
Port:
Beijing/Shenzhen/Shanghai
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Beijing, China (Mainland)
Brand Name:
GFUVE
Model Number:
GF102
Power:
Electronic
Usage:
Auto Testing Machine
GF102:
Single phase watt-hour meter calibrator
Accuracy class:
0.1% /0.2%
Test voltage output (Phase-Neutral):
0V~ 264V
Power of the voltage output:
Max. 30VA , 15VA
Resolution:
0.01%
Accuracy:
0.1% , 0.2%
Stability:
0.02%/120s , 0.05%/120s
Distortion factor:
< 0.3% for linear resistance load
Test current output:
1mA ~120A , 1mA ~60A
Power of the current output:
Max. 100VA , 30VA
Packaging & Delivery
Packaging Details
Inside a layer of aluminum alloy box, outside is packed in wooden cases
Delivery Time
12days upon receipt of firm order

Features of  Single phase test bench GFUVE GF102 watt-hour meter calibrator,CE,ISO9001:2008,IEC approved

  • Meter under testing: 1P2W
  • Testing mode: active power, reactive power
  • Test 3pcs or 2pcs meter synchronously
  • Starting test and creeping test
  • Reference standard and power source integrated, easy to carry.  
  • Measuring mechanical meter and electric meter
  • Operating by manual keyboard or PC
  • With shortcut key of normal test point, speed up testing 
  • Internal large capacity storage device for mass memory
  • Local checking the testing result
  • Overload, short circuit, open circuit protection
  • With self-checking function

Technical Data

Voltage

Test voltage output (Phase-Neutral)

0V – 264V

Power of the voltage output

Max. 30VA , 15VA

Resolution

0.01%

Accuracy

0.1% , 0.2%

Stability

0.02%/120s , 0.05%/120s

Distortion factor

< 0.3% for linear resistance load

Current

Test current output

1mA – 120A , 1mA – 60A

Power of the current output

Max. 100VA , 30VA

Resolution

0.01%

Accuracy

0.1% , 0.2%

Stability

0.02%/120s

Distortion factor

< 0.3% for linear resistance load

Phase angle

Range

0 -- 360°

Resolution

0.1°

Accuracy

0.2°

Frequency

Range

45Hz – 65Hz

Resolution

0.005Hz

Pulse output

High frequency output(CH)

1.666×105 Hz

Low frequency output(CL)

5×10-5×CH

Pulse input

Input channel

3

Input frequency

Max. 20Hz

Other

Voltage Supply

220V±10% 50/60Hz±2Hz

Ambient temperature

-10°C -- +40°C

Relative humidity

35% -- 85%

Dimensions (W×D×H) (mm)

445×440×180 , 410×220×150

Weight (kg)

18 , 9.5

 

Certifications